SOFTWARE LEAD/LAG FU NCTION SHALL ALLOW EITHER OF THE CHILLED WATER PUMPS TO ACT AS THE LEAD PUMP. 3. DIFFERENTIAL PRESSURE CONTROL. THE OBJECTIVE IS TO ALWAYS HAVE ONE COOLING CONTROL VALVE 80% OPEN SO THE PUMPS OPERATE AT THE LOWEST SPEED AND PRESSURE POSSIBLE TO SATISFY THE CURRENT LOAD.
SEQUENCE OF OPERATION GUIDELINE CHILLED WATER .